标题:Pole-to-Ground Fault Analysis for MMC-HVDC Grid
作者:Zhen He ; Jiabing Hu ; Lei Lin ; Zhiyuan He
摘要:Pole-to-ground (PTG) fault analysis is of vital importance for HVDC grid. However, many factors are not considered in the existing studies, such as the asymmetrical property of PTG fault, the coupling issue between dc transmission lines and the complexity of dc grid's structure. This paper presents a PTG fault analysis method, which is based on common- and differential-mode (CDM) transformation. Similar to the symmetrical component method in ac system, the transformation decomposes the HVDC grid into CDM networks at first. Then, under the perspective of CDM components, a transfer impedance based analysis is performed to obtain the analytical expressions of PTG fault characteristics. The proposed PTG fault analysis method is applicable to arbitrary HVDC grid topologies. And the analytical expressions can give theoretical guidance for fault protection. The validity of the proposed PTG fault analysis method is verified by comparison with the simulation results in PSCAD/EMTDC.
发表于:2019 10th International Conference on Power Electronics and ECCE Asia (ICPE 2019 - ECCE Asia)